»  Categories   »      Power Meter   »    Meter   »    Power Quality Analyzer   »    Analyzer  

image enlarge

Fluke 43B Single Phase Power Quality Analyzer

Description

Circuit breakers that trip, transformers that overheat, motors that burn out, machines that don't function properly; whatever the problem, you can quickly and easily identify the cause with the Fluke 43B Power Quality Analyzer.

As a Power Quality Analyzer it is optimized for industrial measurements on the 50 Hz fundamental frequency. Because its frequency range extends from 10 to 400 Hz, it's also ideal for aviation, marine and railway applications.

Besides the unique extended frequency range, the Fluke 43B is the only instrument that combines the capabilities of a Power Quality Analyzer, a 20 MHz oscilloscope, a multimeter and data recorder in a single tool.

Features

  • NiMH Battery provides extended operating time of 6.5 hours
  • Combines the most useful capabilities of a power quality analyzer, multimeter and scope
  • Calculates 3-phase power on balanced loads, from a single-phase measurement
  • Trends voltage, current, frequency, power harmonics and captures voltage sags, transients and inrush current
  • Monitoring functions help track intermittent problems and power system performance
  • Records two selectable parameters for up to 16 days
  • 20 measurement memories to save/recall screens and data with cursor readings
  • FlukeView® software can log harmonics and all other readings over time and provides a complete harmonics profile up to the 51st harmonic
  • Measures resistance, diode voltage drop, continuity, and capacitance
  • Users/applications manual and power quality video to help answer tough questions
  • Complete package with voltage probes and 400 A current clamp, FlukeView Software and optically isolated interface cable

Specifications

V/A/Hz

Usable Bandwidth:

 10 Hz..3.5 kHz

Harmonics on 400Hz fundamental:

 9th

Typical accuracy for 400Hz fundamental:

 5%

Power, battery life

Usable Bandwidth:

 20 Hz..2 kHz

Harmonics on 400Hz fundamental:

 5th

Typical accuracy for 400Hz fundamental:

 10%

Harmonics

Usable Bandwidth:

 10 Hz..3.5 kHz

Harmonics on 400Hz fundamental:

 9th

Typical accuracy for 400Hz fundamental:

 10% channel 1, 50% channel 2

Note

 

 Accuracies are stated as ± (percentage of reading + counts) without probes unless otherwise noted.

 

 Specifications below are valid for signals with a fundamental between 40 and 70 Hz.

Input Characteristics

Input impedance

 1 MΩ, 20 pF

Voltage rating

 600V rms, CAT III

V/A/Hz Display

True-rms voltage (ac + dc)

 

Ranges:

 5.000 V, 50.00 V, 500.0 V, 1250 V*

Accuracy:

 ±(1% + 10 counts)

 

 

True-rms current (ac + dc)

 

Ranges:

 50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA

Accuracy:

 ±(1% + 10 counts)

 

 

Frequency

 

Ranges:

 40.0 to 15.9 kHz

Accuracy:

 ±(0.5% + 2 counts)

 

 

CF Crest factor

 

Ranges:

 1.0 - 10.0

Accuracy:

 ±(0.5% + 1 count)

Power Display

Watts, VA, VAR

 

 

 1-phase and 3-phase,3 conductor balanced loads

Ranges:

 250 W - 1.56 GW

Accuracy:

 ±(4% + 4 counts) Fundamental Power

Accuracy:

 ± (2 % + 6 counts) Total Power

 

 

Power Factor

 

Range:

 0 - 1.0

Accuracy:

 ±0.04

Displacement Power Factor, Cos .F

 

Range:

 0.25 - 0.9

Accuracy:

 ±0.04

Range:

 0.90 - 1.0

Accuracy:

 ±0.03

 

 

Frequency Fundamental

 

Ranges:

 40.0 to 70.0 Hz

Accuracy:

 ±(0.5% + 2 counts)

Harmonics Display

Voltage, Current, Frequency

 

Ranges:

 Fundamental to 51st harmonic

Accuracy:

 

Fundamental:

 VA ±(3% + 2 counts) W ±(5% + 2 counts)

2 to 31st harmonic:

 VA ±(5% +3 counts) W ±(10% +10 counts)

32 to 51st harmonic:

 VA ±(15% +5 counts) W ±(30% +5 counts)

 

 

Frequency Fundamental

 

Ranges:

 40 Hz to 70 Hz

Accuracy:

 ±0.25 Hz

 

 

Phase

 

Range:

 V, A (between Fundamental & Harmonics)

Accuracy:

 ±3º to ±15º

Range:

 W (between Voltage Fundamental & Current Harmonics)

Accuracy:

 ±5º to ±15º

 

 

K-factor (Current and Power)

 

Range:

 1.0 to 30.0

Accuracy:

 ±10%

 

 

THD Total Harmonic Distortion

 

Range:

 0.00 - 99.99

Accuracy:

 ±(3% + 8 counts)

Sags and Swells

Recording times:

 4 min to 16 days (selectable)

Vrms Actual, Vrms max, min(AC + DC)

 

Ranges:

 5.000V, 50.00V, 500.0V, 1250V*

Accuracy:

 Readings ±(2% +10 counts); Cursor readings ± (2% + 12 counts)

 

 

Arms Actual, Arms max, min (AC + DC)

 

Ranges:

 50.00A, 500.0A, 5.000 kA, 50.00 kA

Accuracy:

 ±(2% +10 counts)

Transient Capture

Minimum pulse width:

 40 ns

Useful bandwidth input 1:

 DC to 1 MHz

Number of transients:

 40

Voltage threshold settings:

 20%, 50%, 100%, 200% above or below reference

R, C, Diode, Continuity

Resistance ranges:

 500.0 Ω, 5.000 kΩ, 50.00 kΩ, 500.0 kΩ, 5.000 MΩ, 30.00 MΩ

Resistance accuracy:

 ±(0.6% + 5 counts)

Capacitance ranges:

 50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF

Capacitance accuracy:

 ±(2% + 10 counts)

Diode voltage:

 Accuracy ±(2% + 5 counts)

Continuity:

 Beeper on at < 30 Ω ± 5 Ω

Max current:

 0.5 mA

Inrush Current

Inrush times:

 1 s, 5 s, 10 s, 50 s, 100 s, 5 min

Current ranges:

 1 A, 5 A, 10 A, 50 A, 100 A, 500 A, 1000 A

Accuracy:

 ±5% of full scale

Temperature (with accessory)

Range:

 -100 °C - 400 °C

Accuracy:

 ±(0.5% + 5 counts)

Scope Display

Measurements:

 dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle, phase, pulse width, crest factor

Time ranges:

 20 ns/div to 60 s/div

Max sampling rate:

 25 MS/s

Bandwidth

 

Voltage channel [1]:

 20 MHz at inputs, 20 MHz with VPS40 probe (included with Fluke43B), 1 MHz with TL24 Leads

Current channel [2]:

 15 kHz at inputs, 10 kHz with included clamps

Coupling:

 AC, DC (10 Hz - 3 dB)

Vertical sensitivity:

 5 mV/div to 500V/div

Vertical resolution:

 8 bit (256 levels)

Record length:

 512 samples per channel

Timebase modes:

 Normal, roll, single

Pre-trigger:

 Up to 10 divisions

Trigger Source:

 Input 1 or Input 2 or automatic selection

Trigger Mode:

 Automatic Connect-and-View™, Free Run, and Single Shot

 

 

Connect-and-View™:

 Advanced automatic triggering that recognizes signal patterns

 

 Automatically adjusts triggering, timebase and amplitude and displays stable pictures

Memories

 

 20 (screens, settings, data)

Recording

Recording times:

 4 min to 16 days (selectable)

Parameters:

 Choose one or two parameters from one of the groups below:

 

 Volts/Ampères/Hertz

 

 Watts, VA, VAR, PF, DPF, Frequency

 

 Harmonics, THD, Volts (Fund. & Harmonic), Ampères (F&H) Watts(F&H)

 

 Frequency (H), %(H) of total, Phase(H), KF

 

 Temperature

 

 Resistance, Diode, Continuity, Capacitance

 

 Scope: DC Voltage, DC Current, AC Voltage, AC Current, Frequency,

 

 Pulse Width + or -, Phase, Duty cycle + or -, Peak max, Peak min, Peak min-max, Crest Factor

Note

 

 *Rated EN 61010-1 600 V CAT II CSA

Environmental Specifications

Operating Temperature

 

 0 °C to +50 °C

Safety Specifications

Electrical Safety

 

 EN 61010-1 CAT II, 600V. CSA listed

Mechanical & General Specifications

Size

 

 232 x 115 x 50 mm

Weight

 

 1.1 kg

Warranty

 

 3 years

Battery Life

 

 Rechargeable Ni-MH pack (charger included)

Operating time:

 6.5 hours

Charging time:

 7 hours

Shock & Vibration

 

 Mil 28800E, Type 3, Class III, Style B

Case

 

 IP51 (dust, drip, waterproof)

Standards

CISPR
CISPR 11
CISPR 14 - 1
CISPR 14 - 2
CISPR 14 - 2
CISPR 16 - 1
CISPR 16 - 2
CISPR 16 - 3
CISPR 16 - 4
CISPR 22
CISPR 24
IEC
IEC/TR EN 61000 - 1 - 1
IEC/TR EN 61000 - 2 - 1
IEC/TR EN 61000 - 2 - 3
IEC EN 61000 - 3 - 2
IEC EN 61000 - 3 - 4
IEC/TC EN 61000 - 3 - 5
IEC EN 61000 - 4 - 2
IEC EN 61000 - 4 - 3
IEC EN 61000 - 4 - 4
IEC EN 61000 - 4 - 5
IEC EN 61000 - 4 - 6
IEC EN 61000 - 4 - 7
IEC EN 61000 - 4 - 8
IEC EN 61000 - 4 - 9
IEC EN 61000 - 4 - 11
European
EN 50 081 part 1
EN 50 081 part 2
EN 55 011
EN 55 013
EN 55 014
EN 55 015
EN 55 020
EN 55 022
EN 55 024
EN 50 082 part 1
EN 50 082 part 2
EN 50 093
American
FCC Part 15
MIL-STD - 461E