»  Categories   »      Insulation Meter   »    Meter  

image enlarge

Fluke 1550C/Kit Insulation Resistance Tester Kit

Description

The new Fluke 1550C/Kit insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.

Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1550C/Kit is a perfect tool for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.

Features

  • Test voltages up to 5kV provides solutions for all applications
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Voltage breakdown detection alerts the user that voltage is present and gives the voltage reading up to 600 V ac or dc for increased user safety
  • Selectable test voltages in 50 V steps from 250 to 1000 V, and 100 V steps above 1000 V
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Large digital/analog LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2TΩ
  • Timer settings up to 99 minutes for timed tests

Specifications

Insulation resistance measurement

Test voltage (dc)

Range (dc)

Accuracy (± reading)

250 V

< 200 kΩ
200 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ

unspecified
5 %
20 %
unspecified

500 V

  200 kΩ
200 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ

unspecified
5 %
20 %
unspecified

1000 V

 < 200 kΩ
200 kΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ

unspecified
5 %
20 %
unspecified

2500 V

 < 200 kΩ
200 kΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ

unspecified
5 %
20 %
unspecified

5000 V

 < 200 kΩ
200 kΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ

unspecified
5 %
20 %
unspecified

10000 V
(1555 only)

 < 200 kΩ
200 kΩ to 200 GΩ
10 GΩ to 2 TΩ
> 2 TΩ

unspecified
5 %
20 %
unspecified

Bar graph range

0 to 1 TΩ 

Insulation test voltage accuracy

-0 %, +10 % at 1 mA load current

Induced ac mains current rejection

2 mA maximum

Charging rate for capacitive load

5 seconds per μF 

Discharge rate for capacitive load

1.5 s/μF

Leakage current measurement

Range: 1 nA to 2 mA

Accuracy: ± (5 % + 2 nA)

Capacitance measurement

Range: 0.01 uF to 15.00 μF

Accuracy: ± (15 % rdg + 0.03 μF)

Timer

Range: 0 to 99 minutes

Resolution Accuracy:
Setting: 1 minute
Indication: 1 second

Live circuit warning

Warning Range:
30 V to 660 V ac/dc,
50/60 Hz

Voltage Accuracy:
± (15 % + 2 V)

General specifications

Display

75 mm x 105 mm

Power

12 V lead-acid rechargeable battery, Yuasa NP2.8-12

Charger Input (AC)

Charger Input (AC) 85 V to 250 V ac 50/60 HZ 20 VA

This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.

Dimensions

170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in)

Weight

3.6 kg (7.94 lb)

Temperature (operating)

-20 ºC to 50 ºC (-4 ºF to 122 ºF)

Temperature (storage)

-20 ºC to 65 ºC (-4 ºF to 149 ºF)

Humidity

80 % to 31 ºC decreasing linearly to 50 % at 50 ºC

Altitude

2000 m

Enclosure sealing

IP40

Input overload protection

1000 V ac

Electromagnetic compatibility

EN 61326

Standards

CISPR
CISPR 11
CISPR 14 - 1
CISPR 14 - 2
CISPR 14 - 2
CISPR 16 - 1
CISPR 16 - 2
CISPR 16 - 3
CISPR 16 - 4
CISPR 22
CISPR 24
IEC
IEC/TR EN 61000 - 1 - 1
IEC/TR EN 61000 - 2 - 1
IEC/TR EN 61000 - 2 - 3
IEC EN 61000 - 3 - 2
IEC EN 61000 - 3 - 4
IEC/TC EN 61000 - 3 - 5
IEC EN 61000 - 4 - 2
IEC EN 61000 - 4 - 3
IEC EN 61000 - 4 - 4
IEC EN 61000 - 4 - 5
IEC EN 61000 - 4 - 6
IEC EN 61000 - 4 - 7
IEC EN 61000 - 4 - 8
IEC EN 61000 - 4 - 9
IEC EN 61000 - 4 - 11
European
EN 50 081 part 1
EN 50 081 part 2
EN 55 011
EN 55 013
EN 55 014
EN 55 015
EN 55 020
EN 55 022
EN 55 024
EN 50 082 part 1
EN 50 082 part 2
EN 50 093
American
FCC Part 15
MIL-STD - 461E